Industrial Safety Controls Inc Product
DOLD Relay Extension Module UG 6929
Model: DOLD Relay Extension Module UG 6929
If more safety cicuits have to be switched, than a safety module provides, the extension module UG 6929 is used.
Product description
If more safety cicuits have to be switched, than a safety module provides, the extension module UG 6929 is used. It offers safe and reliable contact multiplication and re-enforcment for safety modules with monitoring of the feedback circuit. Safe semiconductor outputs can be extended by relay output contacts. The extension module has forcibly guided contacts and can be delivered with different contact arrangements.
Technical specifications
| Width: | 22,5 mm |
| Cat. / PL acc. to EN ISO 13849-1: | 4/e |
| SIL acc. to IEC/EN 62061: | 3 |
| Nominal voltage: | AC, AC/DC |
| Thermal current Ith max.: | 8 A |
| 1- / 2-channel: | 1, 2 |
| Connection: | Pluggable screw terminals, Pluggable cage clamp terminals, Pluggable cage clamp terminals 2-wire |
| Output contacts max.: | 1 NC contact, 7 NO contacts |
| Approvals: | UL |
| Type: | UG 6929 |
Advantages
- Safety contact multiplication
Features
- According to
- Performance Level (PL) e and category 4 to EN ISO 13849-1
- SIL Claimed Level (SIL CL) 3 to IEC/EN 62061
- Safety Integrity Level (SIL) 3 to IEC/EN 61508 and IEC/EN 61511 when connected to a suitable safety module - According to EN 50156-1 for furnaces
- Control with safety semiconductor outputs (light curtain, e-stop) possible
- Redundant and forcibly guided contacts
- Output: max.7 NO or 6 NO contacts / 1 NC contact, 1 NC contact for feedback circuit
- 1- or 2-channel
- Indication
- As option with pluggable terminal blocks for easy exchange of devices
- with screw terminals
- or with cage clamp terminals - Width: 22.5 mm
Other Products from Industrial Safety Controls Inc
DOLD Guard lock, Solenoid interlock electromechanical
Guard lock, Solenoid interlock electromechanical Electromechanical solenoid interlocks prevent unauthorized opening of accesses and safety guards Solenoid interlocks of the SAFEMASTER STS
Smart motorstarter with autom. phase sequence correction UG 9256/807
The smart motorstarter UG 9256/804 and UG 9256/807 is used to provide always a clockwise phase sequence